IEC 60947-2, UL 489, Norm NDB2T-63, 3-polig

Available Certifications UL Availability depends on model and configuration.
IEC60947-2 UL489 Standard NDB2T-63 3P(images 1)

Key Specifications/ Special Features:

Applicable scope and purpose

● Short -circuit protection

● Over-load protection

● Control

● Isolation

● DC system protection

NDB2T-63 (UL489) ist für Niederspannungs-Stromverteilungssysteme in der Industrie, in Gebäuden, im Energiesektor, in der Telekommunikation und in der Infrastruktur vorgesehen.

Main technical specification

● Electrical parameters

○ Rated working voltage and relevant breaking capacity:

Pole1P2P3P1P2P3P
Rating current1~32A35~63A
ItemIcu
VoltageAC 120V10kA10kA
AC 240V10kA10kA10kA10kA
AC 277V10kA
AC 480Y/277V10kA10kA
DC60V10kA10kA10kA10kA
DC125V10kA10kA

○ Impulse withstand test voltages: 4kV

○ electrical endurance: 10000 times;Mechanical endurance: 20000 times

●  Product certification and implementation standard.:

○ Product certificate:UL489;

○ Product certification standard:UL489;

●  Environmental requirements:RoHS

●  Isolation function

○ Practical breaking instructions

○ View window within the green identification said contact in the off position

●  Tripping characteristic B type curve

○   Protection of short circuit current small load

○   rated current:1A~63A

○   tripping characteristic:The instantaneous tripping range 4In(1±20%) C type curve

○  Protect normal load and distribution wire cable

○   rated current:1A~63A

○   tripping characteristic:The instantaneous tripping range 8In(1±20%) D type curve

○   Protect starting current big impact load(Such as motor, transformer)

○   rated current:1A~63A

○   tripping characteristic:The instantaneous tripping rang 12In(1±20%)

5、Normal working environment

● Ambient temperature:-40℃~+70℃

● Air relative humidity:≤95%

● Altitude:≤2000m

● pollution degree: 3

● Service place without significant vibration and impact

● Lower capacity coefflcient table above 2000 meters above sealevel

IEC60947-2 UL489 Standard NDB2T-63 3P(images 2)

● Side-by-side volume reduction coefflcient table

IEC60947-2 UL489 Standard NDB2T-63 3P(images 3)

6.  Tripping characteristic

IEC60947-2 UL489 Standard NDB2T-63 3P(images 4)

7、Outline dimensions

IEC60947-2 UL489 Standard NDB2T-63 3P(images 5)

                                                                   3P

8、Mounting

Modular construction,can be installed in EN60715 TH 35mm x 7.5mm standard guide rail.

9、Connect line requirements

○    Standard cross-sections of round copper conductors: 1~35mm2

○  Terminal screw: M5 ,Rated torque : 2.0N.m

11 、 Notice

1、Customers who disassemble the product without approval shall undertake relevant quality problems by themselves;

2、Do not touch the naked part of conductive components when the product is power on;

3、Don’t test characteristics of the breaker optionally, the manufacturer is irresponsible for such quality problems;

4、Keep wiring correct to prevent malfunction or damage of wiring terminals.

5、Please open the cover when installing the accessory. Please refer to OF2, SD2, MX+OF2 Instruction for details.

LAST: WEITER:

Ähnliche Empfehlungen

  • NDB1LE-63 RCBO Typ B mit Überstromschutz

    745

    NDB1LE-63 type B residual current circuit breaker with overcurrent protection provide protection for sinusoidal AC residual current, pulsating DC residual current, composite residual current, and smooth DC residual current at frequencies up to 1kHz.

    Details anzeigen
  • Sekundärstation

    87

    Secondary Unit Substation is a complete integrated power distribution solution designed to receive medium-voltage power, transform it to low voltage, and distribute it safely to downstream electrical loads. It normally combines medium-voltage swit...

    Details anzeigen
  • NDM3-100 4P

    1122

    Part No.:NDM3-100 4P ● Product Details Model Number: NDM3-100 4P Brand Name: Nader Origin: China (mainland) Small Orders: Accepted ● Use & Scope of ApplicationThisAircircuit&nb...

    Details anzeigen
  • NDM2E-250(M,H)

    1127

    1. Applicable Scope and Purpose of Circuit Breaker The NDM2E-250 series of electronic molded case circuit breakers (hereinafter referred to as circuit breakers) apply to infrequent switching of circuits with the AC 50Hz, the working voltage of A...

    Details anzeigen
Mehr erfahren!

Liste der Beratungsangebote
Liste der Beratungsangebote Anfrage zu den oben genannten Produkten senden