Available Certifications UL Availability depends on model and configuration.
IEC60947-2 UL489 Standard NDB2T-63 3P(images 1)

Key Specifications/ Special Features:

Applicable scope and purpose

● Short -circuit protection

● Over-load protection

● Control

● Isolation

● DC system protection

NDB2T-63 (UL489) được thiết kế dành riêng cho hệ thống phân phối điện áp thấp trong các lĩnh vực công nghiệp, tòa nhà, năng lượng, viễn thông và hạ tầng.

Main technical specification

● Electrical parameters

○ Rated working voltage and relevant breaking capacity:

Pole1P2P3P1P2P3P
Rating current1~32A35~63A
ItemIcu
VoltageAC 120V10kA10kA
AC 240V10kA10kA10kA10kA
AC 277V10kA
AC 480Y/277V10kA10kA
DC60V10kA10kA10kA10kA
DC125V10kA10kA

○ Impulse withstand test voltages: 4kV

○ electrical endurance: 10000 times;Mechanical endurance: 20000 times

●  Product certification and implementation standard.:

○ Product certificate:UL489;

○ Product certification standard:UL489;

●  Environmental requirements:RoHS

●  Isolation function

○ Practical breaking instructions

○ View window within the green identification said contact in the off position

●  Tripping characteristic B type curve

○   Protection of short circuit current small load

○   rated current:1A~63A

○   tripping characteristic:The instantaneous tripping range 4In(1±20%) C type curve

○  Protect normal load and distribution wire cable

○   rated current:1A~63A

○   tripping characteristic:The instantaneous tripping range 8In(1±20%) D type curve

○   Protect starting current big impact load(Such as motor, transformer)

○   rated current:1A~63A

○   tripping characteristic:The instantaneous tripping rang 12In(1±20%)

5、Normal working environment

● Ambient temperature:-40℃~+70℃

● Air relative humidity:≤95%

● Altitude:≤2000m

● pollution degree: 3

● Service place without significant vibration and impact

● Lower capacity coefflcient table above 2000 meters above sealevel

IEC60947-2 UL489 Standard NDB2T-63 3P(images 2)

● Side-by-side volume reduction coefflcient table

IEC60947-2 UL489 Standard NDB2T-63 3P(images 3)

6.  Tripping characteristic

IEC60947-2 UL489 Standard NDB2T-63 3P(images 4)

7、Outline dimensions

IEC60947-2 UL489 Standard NDB2T-63 3P(images 5)

                                                                   3P

8、Mounting

Modular construction,can be installed in EN60715 TH 35mm x 7.5mm standard guide rail.

9、Connect line requirements

○    Standard cross-sections of round copper conductors: 1~35mm2

○  Terminal screw: M5 ,Rated torque : 2.0N.m

11 、 Notice

1、Customers who disassemble the product without approval shall undertake relevant quality problems by themselves;

2、Do not touch the naked part of conductive components when the product is power on;

3、Don’t test characteristics of the breaker optionally, the manufacturer is irresponsible for such quality problems;

4、Keep wiring correct to prevent malfunction or damage of wiring terminals.

5、Please open the cover when installing the accessory. Please refer to OF2, SD2, MX+OF2 Instruction for details.

LAST: TIẾP THEO:

Các đề xuất liên quan

  • NDGR3A-800 Isolating Switch

    975

    Applications: NDG3A series of disconnecting switches are applicable to electric systems with a rated voltage not higher than DC 1000V or AC 800V and a rated current not higher than 500A, 630A, 800A. They can be connected and disconnected a...

    Xem chi tiết
  • Trạm biến áp cấp hai

    83

    Secondary Unit Substation is a complete integrated power distribution solution designed to receive medium-voltage power, transform it to low voltage, and distribute it safely to downstream electrical loads. It normally combines medium-voltage swit...

    Xem chi tiết
  • Bảng điều khiển LV

    100

    LV Switchboard, also known as UL 891 Low Voltage Switchboard, is an important low-voltage power distribution product used to receive and distribute electrical power from transformers, generators, low-voltage switchgear, or other power sources to ...

    Xem chi tiết
  • NDM2-63

    969

    1. Applicable Scope and Purpose of Circuit Breaker The NDM2-63 molded case circuit breaker (hereinafter referred to as circuit breaker) applies to infrequent switching of circuits with the AC 50/60Hz, the working voltage of AC415V and working cu...

    Xem chi tiết
Xem thêm!

Danh sách sản phẩm tham khảo
Danh sách sản phẩm tham khảo Gửi yêu cầu tư vấn về các sản phẩm trên