PVSP-108H-410~430M10
1052Ayrıntıları görüntüle

Applicable scope and purpose
● Short -circuit protection
● Over-load protection
● Control
● Isolation
● DC system protection
NDB2T-63 (UL489), endüstri, binalar, enerji, iletişim ve altyapı alanlarındaki alçak gerilim güç dağıtım sistemlerine yöneliktir.
Main technical specification
● Electrical parameters
○ Rated working voltage and relevant breaking capacity:
| Pole | 1P | 2P | 3P | 1P | 2P | 3P | |
| Rating current | 1~32A | 35~63A | |||||
| Item | Icu | ||||||
| Voltage | AC 120V | 10kA | — | — | 10kA | — | — |
| AC 240V | — | 10kA | 10kA | — | 10kA | 10kA | |
| AC 277V | 10kA | — | — | — | — | — | |
| AC 480Y/277V | — | 10kA | 10kA | — | — | — | |
| DC60V | 10kA | 10kA | — | 10kA | 10kA | — | |
| DC125V | — | 10kA | — | — | 10kA | — | |
○ Impulse withstand test voltages: 4kV
○ electrical endurance: 10000 times;Mechanical endurance: 20000 times
● Product certification and implementation standard.:
○ Product certificate:UL489;
○ Product certification standard:UL489;
● Environmental requirements:RoHS
● Isolation function
○ Practical breaking instructions
○ View window within the green identification said contact in the off position
● Tripping characteristic B type curve
○ Protection of short circuit current small load
○ rated current:1A~63A
○ tripping characteristic:The instantaneous tripping range 4In(1±20%) C type curve
○ Protect normal load and distribution wire cable
○ rated current:1A~63A
○ tripping characteristic:The instantaneous tripping range 8In(1±20%) D type curve
○ Protect starting current big impact load(Such as motor, transformer)
○ rated current:1A~63A
○ tripping characteristic:The instantaneous tripping rang 12In(1±20%)
5、Normal working environment
● Ambient temperature:-40℃~+70℃
● Air relative humidity:≤95%
● Altitude:≤2000m
● pollution degree: 3
● Service place without significant vibration and impact
● Lower capacity coefflcient table above 2000 meters above sealevel

● Side-by-side volume reduction coefflcient table

6. Tripping characteristic

7、Outline dimensions

3P
8、Mounting
Modular construction,can be installed in EN60715 TH 35mm x 7.5mm standard guide rail.
9、Connect line requirements
○ Standard cross-sections of round copper conductors: 1~35mm2
○ Terminal screw: M5 ,Rated torque : 2.0N.m
11 、 Notice
1、Customers who disassemble the product without approval shall undertake relevant quality problems by themselves;
2、Do not touch the naked part of conductive components when the product is power on;
3、Don’t test characteristics of the breaker optionally, the manufacturer is irresponsible for such quality problems;
4、Keep wiring correct to prevent malfunction or damage of wiring terminals.
5、Please open the cover when installing the accessory. Please refer to OF2, SD2, MX+OF2 Instruction for details.
Application ●Short -circuit protection ●Over-load protection ●Isolation NDB1-63 dedicated to the low voltage power distribution system of industrial, buildings, energy communications and infrastructure. Specification: 1P+N:AC230/240V; 2P:AC400/...
Ayrıntıları görüntüleApplications: NDG2-200/3 Switch Disconnector is applicable to the low-voltage distribution or motor network under AC 50Hz, rated working voltage of AC400V and AC690V and rated working current of 200A for disconnection of infrequent co...
Ayrıntıları görüntüle