Disjoncteur à boîtier moulé NDM5-1600H

Available Certifications CE Availability depends on model and configuration.
NDM5-1600H Molded Case Circuit Breaker(images 1)

The NDM5-1600 series of moulded case circuit breakers (referred to as circuit breakers) have a rated insulation voltage of 1000V and apply to circuits with the AC 50Hz/60Hz, the rated working voltageAC380/400/415V、AC500V、AC660/690V、AC800V,Vand rated working current (800A to 1250A). The circuit breakers are used for distributing power while protect the overload, short circuit and under-voltage (with a under-voltage release) of lines and power units as well as the infrequent starting, braking, overload and short circuit of motors.
Each voltage level and short-circuit section capacity of the circuit breaker can be connected with the lower incoming line.(Except AC800V )

Technical Parameters

ModleNDM5-1600
Frame current Inm(A)1600
Rated voltage Ue(V)AC380/400/415、500、660/690、800
Rated current In(A)800、1000、1250
Rated insulation voltage Ui V)1000
Power frequency withstand voltage(V)3500
Rated impulse withstand voltage Uimp(kV)12
Number of poles33、43
Interrupting level codeLMH
Rated      limit short-circuit breaking capacity Icu (kA)AC380/400/415V70100100
AC500V507085
AC660/690V203550
AC800V//30
Rated operating short-circuit breaking capacity Ies (kA)AC380/400/415V70100100
AC500V507070
AC660/690V203542
AC800V//20
Usage categoryA
            Operational performance (times)  Mechanical lifeMaintainable free life  10000(3P)/6000(4P)
Maintainable life20000(3P)/12000(4P)
      Electrical lifeAC415V3000
AC500V1500
AC690V1000
AC800V500
BoundaryL(mm)268
NDM5-1600H Molded Case Circuit Breaker(images 2)
NDM5-1600H Molded Case Circuit Breaker(images 3)
NDM5-1600H Molded Case Circuit Breaker(images 4)
NDM5-1600H Molded Case Circuit Breaker(images 5)

Normal Working Environment of Circuit Breaker
1) The altitude of the installation site doesn’t exceed 2,500m. See the “High-altitude DeratingFactor Table of Circuit Breaker” for the derating factor at the altitude;
2) The ambient temperature is -35℃ ~ + 70℃; the average within 24 h shall not be more than+35℃. If the ambient temperature is higher than +40℃, the user needs to reduce the capacity.See the “Derating Factor Table of Temperature Change for the Circuit Breaker” for the derating factor;
3) Its relative humidity at an ambient temperature of +40℃ should not exceed 50%. A higherrelative humidity is allowed at a lower temperature. For example, the relative humidity at20℃ can reach 90%; for frost due to temperature change, the corresponding measuresshould be taken;
4) The product can withstand the effects of wet air, salt mist, oil mist and mould;
5) The installation category of the circuit breaker connected to the main loop is: Category Ⅲ (power distribution and control level), The installation category of the circuit breaker notconnected to the main loop is: Category Ⅱ (load level);
6) The pollution level is Level 3;
7) Degree of protection: IP 20;
8) The product should be installed in places that are free from explosive media, media corrosiveto metal, insulation damaging gas, and conductive dust, which should be also avoided fromsnow and rain;
9) In case of stricter user conditions than the above description, negotiate with the manufacturer.

LAST : SUIVANT :

Recommandations connexes

  • NDM3-100 4P

    1105

    Key Specifications/ Special Features: ACB with multiple protection function in do high precise of selective protection at the same time, also can avoid unnecessary suddenpower failure, improve the reliability, security, power supply system. Part...

    Voir les détails
  • NDQ3-800

    1169

    1. Applicable Scope and Purpose The NDQ3-800 P-grade ATSE are applicable for sites with the AC voltage below AC380V.AC400V.AC415V and the rated frequency of 50Hz. This product complies with the GB14048.1-2012 and GB/T14048.11-2016 standards in acc...

    Voir les détails
  • Appareillage LV

    92

    LV Switchgear, also known as UL 1558 Low Voltage Switchgear, is a key low-voltage power distribution product used for receiving, distributing, controlling, and protecting electrical energy in low-voltage systems. It is commonly installed on the l...