NDB1-32 series MCB is used in low voltage electrical distribution system in industry, business, power, and telecom and construction field.
2.Model and implication
Nader Brand
MCB DesignCode
Frame Size 32A
Tripping Curve C Curve
Rated current(A) 6、10、16
PolesEmpty =1P+N
20、25、32
3.Main technical parameters
●Electrical parameters
○Rated working voltage (Ue): AC230V ○Rated current (In): 6A、10A、16A、20A、25A、32A ○Rated breaking capability: 4.5kA ○Rated operating capability : 4.5kA ○Impulse voltage endurance: 4kV
○Rated Insulation Voltage: 400V
●Mechanical & electrical endurance: 16000 times electrical endurance: 5000 times;Mechanical endurance: 10000 times
●Wiring ○Adopt tunnel type wiring ○Connection capability: 1mm2 to 10 mm2 ○Connection screw M4, Torque: 1.2N.m ●C curve ○Illumination distribution system ○Tripping characteristic: instantaneous trip between 5In to 10In ●Product certification and implementation standard.: ○Product certificate:CCC; ○Product certification standard:GB/T 10963.1,IEC60898-1 ●Environmental requirements:RoHS 4.Working condition ●Ambient temperature: -40℃~+70℃ ●Relative air humidity ≤95% ●Altitude ≤2000m ●Pollution degree: 2 ●Used in place without obvious shock and vibration ●Protection Degree: IP20 5.Tripping curves (reference calibration temperature 30℃)
Type C(5-10)In
6.Outline dimensions and installation
7Mounting Modularized structure can be easily installed in TH35mm×7.5 Standard DIN rail.
8Packaging and storage 9.1Maximum packing quantity 1-pole: 12 pieces in a box, 12 boxes in an overwrap carton. 9.2The products should be stored in the warehouse where there is ventilation. The relative humidity there should not exceed 80%, and the ambient temperature there is between -40℃ to +80℃. In addition, there should not be acidic, alkaline and corrosive gas in the air. The products should not be deposited more than 3 years in the above mentioned conditions since the producing date.
10Notices 10.1Manufacturer will take no responsibility for problems caused by disassembly privately. 10.2Attention to live part when the breaker is energized and avoid touching them. 10.3Manufacturer will take no responsibility for the quality problem caused by adjusting the characteristic of the breaker privately. 10.4Wiring properly to avoid mis-trip or terminal burn.
NDB1L-32 is a compact RCBO for low-voltage terminal circuits. It provides overload, short-circuit and residual-current protection while allowing neutral-pole switching in a space-saving 1P+N format. Typical configuration only. Final ratings are co...
NDB1LE-100 is a compact residual-current circuit breaker for low-voltage terminal distribution. It combines overload, short-circuit, earth-leakage and isolation protection in one DIN-rail device. Typical configuration only. Final ratings are conf...
NDB1LE-63 type B residual current circuit breaker with overcurrent protection provide protection for sinusoidal AC residual current, pulsating DC residual current, composite residual current, and smooth DC residual current at frequencies up to 1kHz.
The NDB1LE-63 series of residual current action circuit breakers provide the ground leakage, direct or indirect electric shock by human body and other faults protection, which are applicable to the low -voltage terminal distribution in the industr...
Produktanfrage senden
Wir werden uns innerhalb von 24 Stunden bei Ihnen melden.