NDB1LE-63 Type B RCBO with Overcurrent Protection

Application:
NDB1LE-63 type B residual current circuit breaker with overcurrent protection provide protection for sinusoidal AC residual current, pulsating DC residual current, composite residual current, and smooth DC residual current at frequencies up to 1kHz, applicable to new energy, charging station, intelligent building, industrial control and other occasions where frequency conversion technology is used. NDB1LE-63 type B residual current circuit breaker with overcurrent protection (type B RCBO) has the following functions:

● Short circuit protection
● Overload protection
● Residual current protection (type B)
● Isolation (1PN, 3PN not applicable)

Electrical Parameters:

NDB1LE-63 type B RCBO main technical parameters

StandardGB/T 22794, IEC 62423, EN 62423
CertificateCCC, CB, CE, TUV
Number of Product Poles1PN, 2P3P, 3PN, 4P
Rated Operational Voltage Ue (V)AC230/240AC 400/415
Rated Insulation Voltage Ui (V)500
Rated Impulse withstand Voltage Uimp (kV)4
Residual Tripping Current TypeB
Instantaneous Tripping TypeType C (6A-63A), Type D (6A-40A)
Rated Current In (A)6, 10, 16, 20, 25, 32, 40, 50, 63
Icu (kA effective value)6
Ics (kA effective value)6
Rated residual Operating Current I△n (mA)30
Rated Frequency (Hz)50/60
Electrical Life10000
Mechanical Life20000

Other Parameters:

● Isolating function (1PN, 3PN not applicable)
● Leakage visualization
● Wiring
Tunnel type wiring mode
Wiring capacity: Copper cable 1~25mm²
Standard torsional moment: 2.0N.m

● Protection class
Protection class of the circuit breaker body: IP20
To be installed in the distribution box: IP40

Working Conditions:

● Ambient temperature: -25℃~+60℃
● Storage ambient temperature: -40℃~+80℃
● Damp heat resistance: When the ambient air temperature is 55℃, the relative air humidity is ≤95%

● No more than 2000m, in case of use at the higher altitude, refer to the requirements of the miniature circuit breaker for derating. Refer to GB/T 20645 Special environmental conditions technical requirements for low voltage apparatus used in plateau

● Pollution degree: 2
● Can withstand the effects of salt mist and oil mist
● In a medium without explosion risk, and where the medium is not sufficient to corrode metals and damage insulation with gases and conductive dust

● Damage insulation with gases and conductive dust

The prev: The next:

Related recommendations

  • NDB1-32

    116

    1.Application Protection against short circuit ● Protection against overload ● Control ● Isolation NDB1-32 series MCB is used in low voltage electrical distribution system ...

    View details
  • NDB1LE-100

    59

    Application●Short-circuit protection●Over-load protection●Earth leakage protection●Isolation protectionNDB1LE-40 series residual current unit is applied to protect direct or indirect earth lea...

    View details
  • RCBO NDB1LE-63 C63 Type A

    247

    The NDB1LE-63 series of residual current action circuit breakers provide the ground leakage, direct or indirect electric shock by human body and ot...

    View details
  • NDB1L-32

    98

    1.Application Scope and Purpose ●Short-circuit protection●Overload protection●Current leakage protection●Isolation protectionThe NDB1L-32 series of residual current action circuit breakers ...

    View details
Click Cancel to reply
    Expand more!
    咨询产品列表
    咨询产品列表 提交咨询以上产品
    咨询产品列表