NDB1LE-63 Type B RCBO with Overcurrent Protection

Application:
NDB1LE-63 type B residual current circuit breaker with overcurrent protection provide protection for sinusoidal AC residual current, pulsating DC residual current, composite residual current, and smooth DC residual current at frequencies up to 1kHz, applicable to new energy, charging station, intelligent building, industrial control and other occasions where frequency conversion technology is used. NDB1LE-63 type B residual current circuit breaker with overcurrent protection (type B RCBO) has the following functions:

● Short circuit protection
● Overload protection
● Residual current protection (type B)
● Isolation (1PN, 3PN not applicable)

Electrical Parameters:

NDB1LE-63 type B RCBO main technical parameters

StandardGB/T 22794, IEC 62423, EN 62423
CertificateCCC, CB, CE, TUV
Number of Product Poles1PN, 2P3P, 3PN, 4P
Rated Operational Voltage Ue (V)AC230/240AC 400/415
Rated Insulation Voltage Ui (V)500
Rated Impulse withstand Voltage Uimp (kV)4
Residual Tripping Current TypeB
Instantaneous Tripping TypeType C (6A-63A), Type D (6A-40A)
Rated Current In (A)6, 10, 16, 20, 25, 32, 40, 50, 63
Icu (kA effective value)6
Ics (kA effective value)6
Rated residual Operating Current I△n (mA)30
Rated Frequency (Hz)50/60
Electrical Life10000
Mechanical Life20000

Other Parameters:

● Isolating function (1PN, 3PN not applicable)
● Leakage visualization
● Wiring
Tunnel type wiring mode
Wiring capacity: Copper cable 1~25mm²
Standard torsional moment: 2.0N.m

● Protection class
Protection class of the circuit breaker body: IP20
To be installed in the distribution box: IP40

Working Conditions:

● Ambient temperature: -25℃~+60℃
● Storage ambient temperature: -40℃~+80℃
● Damp heat resistance: When the ambient air temperature is 55℃, the relative air humidity is ≤95%

● No more than 2000m, in case of use at the higher altitude, refer to the requirements of the miniature circuit breaker for derating. Refer to GB/T 20645 Special environmental conditions technical requirements for low voltage apparatus used in plateau

● Pollution degree: 2
● Can withstand the effects of salt mist and oil mist
● In a medium without explosion risk, and where the medium is not sufficient to corrode metals and damage insulation with gases and conductive dust

● Damage insulation with gases and conductive dust

The prev: The next:

Related recommendations

  • RCBO NDB1LE-63 C63 Type A

    80

    The NDB1LE-63 series of residual current action circuit breakers provide the ground leakage, direct or indirect electric shock by human body and ot...

    View details
  • NDQ3HP

    694

    1、Application The NDQ3HP bypass automatic transfer switching equipment applies to the automatic transfer between two-way power supplies in the emergency power supply system with the AC...

    View details
  • NDM2E-250(M,H)

    680

    1. Applicable Scope and Purpose of Circuit Breaker The NDM2E-250 series of electronic molded case circuit breakers (hereinafter referred to as circuit breakers) apply to infrequent swit...

    View details
Click Cancel to reply
    Expand more!
    咨询产品列表
    咨询产品列表 提交咨询以上产品
    咨询产品列表