NDB1LE-63 RCBO типа B с защитой от перегрузки по току

Available Certifications CE Availability depends on model and configuration.
NDB1LE-63 Type B RCBO with Overcurrent Protection(images 1)

Application:
NDB1LE-63 type B residual current circuit breaker with overcurrent protection provide protection for sinusoidal AC residual current, pulsating DC residual current, composite residual current, and smooth DC residual current at frequencies up to 1kHz, applicable to new energy, charging station, intelligent building, industrial control and other occasions where frequency conversion technology is used. NDB1LE-63 type B residual current circuit breaker with overcurrent protection (type B RCBO) has the following functions:

● Short circuit protection
● Overload protection
● Residual current protection (type B)
● Isolation (1PN, 3PN not applicable)

Electrical Parameters:

NDB1LE-63 type B RCBO main technical parameters

StandardGB/T 22794, IEC 62423, EN 62423
CertificateCCC, CB, CE, TUV
Number of Product Poles1PN, 2P3P, 3PN, 4P
Rated Operational Voltage Ue (V)AC230/240AC 400/415
Rated Insulation Voltage Ui (V)500
Rated Impulse withstand Voltage Uimp (kV)4
Residual Tripping Current TypeB
Instantaneous Tripping TypeType C (6A-63A), Type D (6A-40A)
Rated Current In (A)6, 10, 16, 20, 25, 32, 40, 50, 63
Icu (kA effective value)6
Ics (kA effective value)6
Rated residual Operating Current I△n (mA)30
Rated Frequency (Hz)50/60
Electrical Life10000
Mechanical Life20000

Other Parameters:

● Isolating function (1PN, 3PN not applicable)
● Leakage visualization
● Wiring
Tunnel type wiring mode
Wiring capacity: Copper cable 1~25mm²
Standard torsional moment: 2.0N.m

● Protection class
Protection class of the circuit breaker body: IP20
To be installed in the distribution box: IP40

Working Conditions:

● Ambient temperature: -25℃~+60℃
● Storage ambient temperature: -40℃~+80℃
● Damp heat resistance: When the ambient air temperature is 55℃, the relative air humidity is ≤95%

● No more than 2000m, in case of use at the higher altitude, refer to the requirements of the miniature circuit breaker for derating. Refer to GB/T 20645 Special environmental conditions technical requirements for low voltage apparatus used in plateau

● Pollution degree: 2
● Can withstand the effects of salt mist and oil mist
● In a medium without explosion risk, and where the medium is not sufficient to corrode metals and damage insulation with gases and conductive dust

● Damage insulation with gases and conductive dust

LAST: ДАЛЕЕ:

Связанные рекомендации

  • NDB1-32

    710

    1.Application Protection against short circuit ● Protection against overload ● Control ● Isolation NDB1-32 series MCB is used in low voltage electrical distribution system in industry, business, power, and telecom and construction field. 2.Mo...

    Посмотреть подробности
  • NDB1LE-100

    612

    NDB1LE-100 is a compact residual-current circuit breaker for low-voltage terminal distribution. It combines overload, short-circuit, earth-leakage and isolation protection in one DIN-rail device. Typical configuration only. Final ratings are conf...

    Посмотреть подробности
  • NDB1L-32

    639

    NDB1L-32 is a compact RCBO for low-voltage terminal circuits. It provides overload, short-circuit and residual-current protection while allowing neutral-pole switching in a space-saving 1P+N format. Typical configuration only. Final ratings are co...

    Посмотреть подробности
Узнать больше!

Список продуктов для консультаций
Список продуктов для консультаций Отправить запрос по вышеуказанным товарам