Application Scope and Purpose ● Short-circuit protection ● Overload protection ● Current leakage protection ● Isolation protection
The NDB1LE-63 series of residual current action circuit breakers provide the ground leakage, direct or indirect electric shock by human body and other faults protection, which are applicable to the low -voltage terminal distribution in the industry, civil buildings, energy, communication, infrastructure and other fields.
Main Technical Parameters ● Electrical parameters ● Frequency: 50/60Hz
● Rated working voltage: AC230V/240V (1PN(One protection pole , N pole continued conducting), 2P, C400V/415V(3P, 3PN(Three protection pole , N pole continued conducting), 4P)
● Rated impulse withstand voltage: 4kV ● Rated insulation voltage: 500V ● Residual operating current type: A, AC ● Instantaneous tripping characteristics: Type B, C, D ● Rated working current: 1A, 2A, 3A, 4A, 5A, 6A, 10A, 16A, 20A, 25A, 32A, 40A, 50A, 63A ● Rated short breaking capability(Icn): 6kA ● Rated operating breaking capability(Ics): 6kA ● Rated residual operating current: 30mA, 50mA, 100mA, 300mA ● Mechanical life: 20,000 times ● Electrical life: 10,000 times
● Isolating function ● Leakage visualization
● Protection class Protection class of the circuit breaker body: IP20 To be installed in the distribution box: IP40
Normal Working Environment
Altitude: ≤2000m, In case of use at the higher altitude, refer to the requirements of the miniature circuit breaker for derating. Refer to GB/T20645 “Specific Environmental Condition – T2020.12.18echnical Requirements of Low-voltage Apparatuses for Plateau”.
● Pollution level: 3 ● Using ambient temperature: -25℃~+60℃ ● Wet heat resistance: The humidity should be not more than 95% at 55℃ ● Storage ambient temperature: -40℃~+80℃
● The product can withstand the effects of salt mist and oil mist ● The product can be disposed in places that are free from explosive media, media corrosive to metal, insulation damaging gas, and conductive dust
● The product should be installed free from snow and rain
Packaging and Storage Maximum packaging quantity: (1A~32A(1PN) product: 5 pieces/box, 1A~32A(2P) product: 4 pieces/box, 1A~32A(3P/3PN/4P)product: 2 pieces/box;40A~63A(1PN) product: 4 pieces/box, 40A~63A(2P) product: 3 pieces/box, 40A~63A(3P/3PN)product: 2 pieces/box, 40A~63A (4P) product: 1 piece/box).. The packaged products should be stored in a warehouse with the air ventilation and the relative humidity no more than 80% and the temperature between -40℃ and +80℃. No acidic, alkaline or other corrosive gas exists in the ambient air in the warehouse. Under the above conditions, the storage period shall be no more than three years since the manufacturing date.
NDB1LE-100 is a compact residual-current circuit breaker for low-voltage terminal distribution. It combines overload, short-circuit, earth-leakage and isolation protection in one DIN-rail device. Typical configuration only. Final ratings are conf...
1.Application Protection against short circuit ● Protection against overload ● Control ● Isolation NDB1-32 series MCB is used in low voltage electrical distribution system in industry, business, power, and telecom and construction field. 2.Mo...
NDB1LE-63 type B residual current circuit breaker with overcurrent protection provide protection for sinusoidal AC residual current, pulsating DC residual current, composite residual current, and smooth DC residual current at frequencies up to 1kHz.
NDB1L-32 is a compact RCBO for low-voltage terminal circuits. It provides overload, short-circuit and residual-current protection while allowing neutral-pole switching in a space-saving 1P+N format. Typical configuration only. Final ratings are co...
إرسال استفسار عن المنتج
سنتصل بك في غضون 24 ساعة