RCCB SVL1M-63

RCCB SVL1M-63(images 1)

Specification:

Electrical Features
ModeElectromagnetic
Type (wave form of the earth leakage sensed)B
Rated Current In25, 40, 63A
Poles2P, 4P
Rated Voltage Ue2P 240V~, 4P 415V~
Insulation Voltage Ui500V
Rated Frequency50/60Hz
Rated Residual Operation Current (In)30mA
Rated Residual Operating Current (Idc)6mA
Rated Residual Making & Breaking Capacity (Im)500A (In≤40A), 10In (In>40A)
Short-circuit Current Inc = Ic10000A
SCPD FuseRCCB SVL1M-63(images 2)
Break Time Under In≤0.1s
Rated Impulse Withstand Voltage (1.5/50) Uimp4000V
Dielectric Test Voltage at ind.Freq. for 1min2.5kV
Electrical Life2000 Cycles
Mechanical Life4000 Cycles
 
Installation
Contact Position IndicatorYes
Protection DegreeIP20
Ambient Temperature (with daily average≤35)-25℃~+35℃
Storage Temperature-25℃~+70℃
Terminal Connection TypeCable/Pin-type Busbar/U-type Busbar
Terminal Size top/bottom for Cable35mm2  18~3AWG
Terminal Size top/bottom for Busbar35mm2  18~3AWG
Tightening Torque2.5Nm  22In-lbs
MountingOn DIN Rail EN60715(35mm) by means of fast clip device
ConnectionPower Supply in Both Directions

Tripping Current Range:

Lagging AngleI△n>0.01AI△n≤0.01A
0.35I△n ≤ I△ ≤ 1.4I△n0.35I△n ≤ I△ ≤ 2I△n
90°0.25I△n ≤ I△ ≤ 1.4I△n0.25I△n ≤ I△ ≤ 2I△n
135°0.11I△n ≤ I△ ≤ 1.4I△n0.11I△n ≤ I△ ≤ 2I△n
 
Alternative Current SensitivePulsating Direct Current SensitiveSurge Current Proof
B Class
Tripping is ensured for sinusoidal AC residual currents pulsed DC residual current, alternating residual sinusoidal currents up to 1000Hz, pulsating direct residual currents and for smooth direct residual currents, whether applied suddenly or increasing slowly.
RCCB SVL1M-63(images 3)
They react to AC and pulsating DC fault current which reach 0 or almost 0 within one time period of the mains frequency.
RCCB SVL1M-63(images 4)
RCCB’s surge capacity. Not tripping at standardized 8/20 us surge-current waves acc.to VDE 0432 Part 2 with surge current values of up to 250A.

Overall and Installation Dimension (mm) 

RCCB SVL1M-63(images 5)

Circuit Diagram

RCCB SVL1M-63(images 6)
LAST: التالي:

توصيات ذات صلة

  • NDC1(Z)-65 AC Contactor with AC or DC Coil

    1499

    NDC1(Z)-65 AC Contactor, which used in 50Hz(60Hz) AC circuit with the rated voltage of 1000V. It is used in AC-3 type, with the rated working voltage of 415V and rated working current of 65A, to realize distant connection and disconnection of the ...

    عرض التفاصيل
  • NDM2-400

    1052

    1. Applicable Scope and Purpose of Circuit Breaker The NDM2-400 molded case circuit breaker (hereinafter referred to as circuit breaker) applies to infrequent switching of circuits with the AC 50/60Hz, the working voltage of AC690V and working c...

    عرض التفاصيل
اعرض المزيد!

قائمة المنتجات المتاحة للاستشارة
قائمة المنتجات المتاحة للاستشارة إرسال استفسار بشأن المنتجات المذكورة أعلاه