Hydraulic- magnetic circuit breaker, NDB3-30 Z4 1P Circuit Breaker for Equipment

Application
NDB3-30 series circuit breaker for equipment (hhydraulic-magnetic circuit breaker) is used in the power system with rated current from 0.1A TO 30A, rated voltage up to AC250A(50/60Hz) or DC80V. It provides overload, short circuit protection. It can also be used for infrequent close or open. The application fields are computer and peripheral equipment, industrial automatic control system, telecom equipment, power supply system, UPS, railroad, marine, spacecraft, elevator, portable power supply and so on.
NDB3-30(1)-Z4 (2) 20(3)/2(4) Q(5) H(6) Y1(7)-2(8)-0(9)-R(10)
1 | Frame Size | 30 |
2 | Tripping Curve | Z2 DC short delay Z4 DC medium delay J2 AC short delay J4 AC medium delay |
3 | Rated Current of Standard CBE(A) | 0.1,0.2,0.3,0.4,0.5,0.6,0.7,0.75,0.8,0.9,1,1.5,2,2.5,3,3.5, 4,4.5,5,5.5,6,6.5,7,7.5,8,8.5,9,9.5,10,11,12,13,14,15,16, 17,18,19,20,21,22,23,24,25,26,2728,29,30 |
4 | Rated Current of Lighting | 10,11,12,13,14,15,16,17,18,19,20,21,22,23,24,25,26,27,28,29,30 |
5 | Number of Poles | 1 One Pole 2 Two pole |
6 | Mounting Method | Q Snap-in mounting |
7 | Wiring Method | H Solder-in/ Q.C.tab type C Push-in stud E Screw 8-32UNC type J Screw 8-32unc with upturned lugs P Screw M4 type R Screw M4 with upturned lugs |
8 | Actuator Type Code | Y1 Black ocker, vertical white legend Y2 Black rocker, horizontal white legend Y3 White rocker, vertical black legend Y4 White rocker, horizontal black legend Y5 Orange rocker, vertical black legend Y6 Orange rocker, horizontal black legend Y7 Red rocker, vertical black legend Y7 Red rocker, horizontal black legend |
9 | Case Color Code | 1. Black 2. Gray 3. Black without rocker guard 4. Gray without rocker guard |
10 | Accessory Code | 0 No accessory |
11 | Certificate code | No code TUV,CE, CCC R UL1088, TUV,CE,CCC L UL489A Listed, TUV, CE,CCC |
Standards: | IEC 60934, GB/T 17701, UL1077, UL489A |
Rated Working Voltage(Ue) | AC 250V(50/60Hz), DC80V, DC65V |
Power Frequency Withstand Voltage | 2500V (The withstand voltage of products using in altitude of 4000m is tested under 2500V*1.29 at sea level in the factory) |
Mechanical/ Electrical Endurance | 10000/6000 times |
Tripping Model | Hydraulic-magnetic type |
Trip-free Feature | with trip-free mechanism |
Vibration Test Parameter | sweep frequency 8Hz-500Hz-8Hz within sine wave, accelerated speed is 3g |
Shock Test Parameters | shock pulse period is 30ms, shock is 30g |
Rated Voltage (V) | Frequency | Rated Current (A) | Number of Poles | Breaking Capacity (A) | |||||
3C (GB/T 17701) | UL1077 | UL489A | TUV/CE (EN60934) | ||||||
Inc | Icn | Inc | Icn | ||||||
AC 250V | 50/60Hz | 0.1~30 | 1, 2 | 15000 | 1000 | 1000, U1 | / | 1500 | 1000 |
DC 80V | / | 0.1~30 | 1, 2 | 1000 | 600 | 1000, U1 | / | 1000 | 600 |
DC 65V | 1~30 | 1, 2 | / | 1000 | / | / | / | / | |
DC 80V | / | 0.1~30 | 1 | / | / | / | 600 | / | / |
DC 65V | / | 0.1~30 | 1 | / | / | / | 1000 | / | / |
Working conditions
- Operation temperature: -40℃~+85℃
- Altitude:≤2000m
- Humidity:≤95%
- Service place without explosive media, gas, and dust which are corrosive and conductive
- Be mounted free from rain and snow
Curves/ Current | In | 135%In | 200%In | 600%In | 10000%In |
Z2/J2 | No Trip | 0.3~7 | 0.1~2 | 0.008~0.3 | 0.005~0.1 |
Z4/J4 | No Trip | 3~70 | 1~15 | 0.008~2 | 0.005~0.35 |
Packing and depositing:
- Minimum packing quantity:
- 1-pole: 18 pieces in a box, 12 boxes in an overwrap carton
- 1-pole(Integrated terminal product):12 pieces in a box, 12 boxes in an overwrap carton
- 2-pole:12 pieces in a box, 12 boxes in an overwrap carton
2. The product should be stored in the warehouse where there is ventilation. The relative humidity there should not exceed 80%, and the ambient temperature there is between -25℃ to +60℃. In addition, there should not be acidic, alkaline and corrosive gas in the air. The productss should not be deposited more than 3 years in the above mentioned condition since the producing date.
Related recommendations
-
NDG2-200 3P Isolating Switch
667Applications: NDG2-200/3 Switch Disconnector is applicable to the low-voltage distribution or motor network under AC 50Hz, rated working voltage of AC400V and AC690V and rate...
View details -
NDM2-63
5881. Applicable Scope and Purpose of Circuit Breaker The NDM2-63 molded case circuit breaker (hereinafter referred to as circuit breaker) applies to infrequent switching of circuits with ...
View details -
NDM2-630
8101. Applicable Scope and Purpose of Circuit Breaker The NDM2-630 molded case circuit breaker (hereinafter referred to as circuit breaker) applies to infrequent switching of circuits wi...
View details -
NDC1(Z)-65 AC Contactor with AC or DC Coil
946NDC1(Z)-65 AC Contactor, which used in 50Hz(60Hz) AC circuit with the rated voltage of 1000V. It is used in AC-3 type, with the rated working volta...
View details
HelloPlease log in