RCCB SVL1M-63

Specification:
| Electrical Features | |
| Mode | Electromagnetic |
| Type (wave form of the earth leakage sensed) | B |
| Rated Current In | 25, 40, 63A |
| Poles | 2P, 4P |
| Rated Voltage Ue | 2P 240V~, 4P 415V~ |
| Insulation Voltage Ui | 500V |
| Rated Frequency | 50/60Hz |
| Rated Residual Operation Current (I△n) | 30mA |
| Rated Residual Operating Current (I△dc) | 6mA |
| Rated Residual Making & Breaking Capacity (I△m) | 500A (In≤40A), 10In (In>40A) |
| Short-circuit Current Inc = I△c | 10000A |
| SCPD Fuse | |
| Break Time Under I△n | ≤0.1s |
| Rated Impulse Withstand Voltage (1.5/50) Uimp | 4000V |
| Dielectric Test Voltage at ind.Freq. for 1min | 2.5kV |
| Electrical Life | 2000 Cycles |
| Mechanical Life | 4000 Cycles |
| Installation | |
| Contact Position Indicator | Yes |
| Protection Degree | IP20 |
| Ambient Temperature (with daily average≤35℃) | -25℃~+35℃ |
| Storage Temperature | -25℃~+70℃ |
| Terminal Connection Type | Cable/Pin-type Busbar/U-type Busbar |
| Terminal Size top/bottom for Cable | 35mm2 18~3AWG |
| Terminal Size top/bottom for Busbar | 35mm2 18~3AWG |
| Tightening Torque | 2.5Nm 22In-lbs |
| Mounting | On DIN Rail EN60715(35mm) by means of fast clip device |
| Connection | Power Supply in Both Directions |
Tripping Current Range:
| Lagging Angle | I△n>0.01A | I△n≤0.01A |
| 0° | 0.35I△n ≤ I△ ≤ 1.4I△n | 0.35I△n ≤ I△ ≤ 2I△n |
| 90° | 0.25I△n ≤ I△ ≤ 1.4I△n | 0.25I△n ≤ I△ ≤ 2I△n |
| 135° | 0.11I△n ≤ I△ ≤ 1.4I△n | 0.11I△n ≤ I△ ≤ 2I△n |
| Alternative Current Sensitive | Pulsating Direct Current Sensitive | Surge Current Proof |
| B Class Tripping is ensured for sinusoidal AC residual currents pulsed DC residual current, alternating residual sinusoidal currents up to 1000Hz, pulsating direct residual currents and for smooth direct residual currents, whether applied suddenly or increasing slowly. | They react to AC and pulsating DC fault current which reach 0 or almost 0 within one time period of the mains frequency. | RCCB’s surge capacity. Not tripping at standardized 8/20 us surge-current waves acc.to VDE 0432 Part 2 with surge current values of up to 250A. |
Overall and Installation Dimension (mm)

Circuit Diagram

Related recommendations
-
NDB1LE-100
451Application●Short-circuit protection●Over-load protection●Earth leakage protection●Isolation protectionNDB1LE-40 series residual current unit is applied to protect direct or indirect earth lea...
View details -
Circuit Breaker for Equipment, Oil damping product NDB3-50 J4 2P, Industrial Automatic Control
1023Application NDB3-50 series circuit breaker for equipment (hudraulic-magnetic circuit breaker) is applied in electrical system, of which the rated current is from 0.5A to 63A and the rated v...
View details -
NDW1A 6300
1029Key Specifications/ Special Features: ACB with multiple protection function in do high precise of selective protection at the same time, also can avoid unnecessary suddenpower fai...
View details -
NDQ3HP
11131、Application The NDQ3HP bypass automatic transfer switching equipment applies to the automatic transfer between two-way power supplies in the emergency power supply system with the AC...
View details
Featured Categories
HelloPlease log in