PRODUCT CENTER

RCCB SVL1M-63

Specification:

Electrical Features
ModeElectromagnetic
Type (wave form of the earth leakage sensed)B
Rated Current In25, 40, 63A
Poles2P, 4P
Rated Voltage Ue2P 240V~, 4P 415V~
Insulation Voltage Ui500V
Rated Frequency50/60Hz
Rated Residual Operation Current (In)30mA
Rated Residual Operating Current (Idc)6mA
Rated Residual Making & Breaking Capacity (Im)500A (In≤40A), 10In (In>40A)
Short-circuit Current Inc = Ic10000A
SCPD Fuse
Break Time Under In≤0.1s
Rated Impulse Withstand Voltage (1.5/50) Uimp4000V
Dielectric Test Voltage at ind.Freq. for 1min2.5kV
Electrical Life2000 Cycles
Mechanical Life4000 Cycles
 
Installation
Contact Position IndicatorYes
Protection DegreeIP20
Ambient Temperature (with daily average≤35)-25℃~+35℃
Storage Temperature-25℃~+70℃
Terminal Connection TypeCable/Pin-type Busbar/U-type Busbar
Terminal Size top/bottom for Cable35mm2  18~3AWG
Terminal Size top/bottom for Busbar35mm2  18~3AWG
Tightening Torque2.5Nm  22In-lbs
MountingOn DIN Rail EN60715(35mm) by means of fast clip device
ConnectionPower Supply in Both Directions

Tripping Current Range:

Lagging AngleI△n>0.01AI△n≤0.01A
0.35I△n ≤ I△ ≤ 1.4I△n0.35I△n ≤ I△ ≤ 2I△n
90°0.25I△n ≤ I△ ≤ 1.4I△n0.25I△n ≤ I△ ≤ 2I△n
135°0.11I△n ≤ I△ ≤ 1.4I△n0.11I△n ≤ I△ ≤ 2I△n
 
Alternative Current SensitivePulsating Direct Current SensitiveSurge Current Proof
B Class
Tripping is ensured for sinusoidal AC residual currents pulsed DC residual current, alternating residual sinusoidal currents up to 1000Hz, pulsating direct residual currents and for smooth direct residual currents, whether applied suddenly or increasing slowly.

They react to AC and pulsating DC fault current which reach 0 or almost 0 within one time period of the mains frequency.

RCCB’s surge capacity. Not tripping at standardized 8/20 us surge-current waves acc.to VDE 0432 Part 2 with surge current values of up to 250A.

Overall and Installation Dimension (mm) 

Circuit Diagram

The prev: The next:

Related recommendations

  • NDM5-1600H Molded Case Circuit Breaker

    412

    The NDM5-1600 series of moulded case circuit breakers (referred to as circuit breakers) have a rated insulation voltage of 1000V and apply to circuits with the AC 50Hz/60Hz, the rated working ...

    View details
  • NDQ3-125

    659

    1. Applicable Scope and Purpose The NDQ3-125 P-grade ATSE are applicable for sites with the AC voltage below AC380V.AC400V.AC415V and the rated frequency of 50Hz. This product...

    View details
  • NDM2E-400

    647

    1. Applicable Scope and Purpose of Circuit Breaker The NDM2E-400 series of electronic molded case circuit breakers (hereinafter referred to as circuit breakers) apply to infrequent swit...

    View details
  • NDG2-200 3P Isolating Switch

    667

    Applications: NDG2-200/3 Switch Disconnector is applicable to the low-voltage distribution or motor network under AC 50Hz, rated working voltage of AC400V and AC690V and rate...

    View details
Click Cancel to reply
    Expand more!
    咨询产品列表
    咨询产品列表 提交咨询以上产品
    咨询产品列表