NDM3A-630 Molded Case Circuit Breaker

The NDM3A-630 molded case circuit breaker (hereinafter referred to as circuit breaker) appliesto infrequent switching of circuits with the AC 50/60Hz, the working voltage of AC1000V and working current of 630A as well as infrequent motor starting. With the overload, short circuit and undervoltage protection functions, the circuit breaker can protect lines and power equipment from damage.
Technical Parameters
Model | NDM3A-630 | ||
Rated current of frame Inm(A) | 630 | ||
Rated current In(A) | 400,500,630 | ||
Rated insulation voltage Ui(AC V) | 1140 | ||
Rated impulse withstand voltage Uimp (V) | 8000 | ||
Rated working voltage Ue (AC V) | 550,600,690,800,1000 | ||
Power frequency withstand voltage U(1min)(V) | 3500 | ||
Utilization category | A | ||
Number of poles | 3 | ||
Breaking capacity level | M | ||
Rated limit short-circuit breaking capacity Icu (kA) | AC550V | 50 | |
AC600V | 42 | ||
AC690V | 35 | ||
AC800V | 30 | ||
AC1000V | 12 | ||
Rated operating short-circuit breaking capacity Ics (kA) | AC550V | 50 | |
AC600V | 42 | ||
AC690V | 35 | ||
AC800V | 23 | ||
AC1000V | 12 | ||
Operating performance (times) | Electrical life | AC550V | 4000 |
AC600V | 2500 | ||
AC690V | 2000 | ||
AC800V | 1500 | ||
AC1000V | 1000 | ||
Mechanical Life | Maintainable Free Life | 10000 | |
Maintainable Life | 20000 |
Normal Working Environment
1)The altitude of the installation site doesn’t exceed 2,500m. See the “High-altitude DeratingFactor Table of Circuit Breaker” for the derating factor at the altitude;
2)The ambient temperature is -35℃ ~ + 70℃; the average within 24 h shall not be morethan +35℃. If the ambient temperature is higher than +40℃, the user needs to reduce thecapacity. See the “Derating Factor Table of Temperature Change for the Circuit Breaker”for the derating factor;
3)Its relative humidity at an ambient temperature of +40℃ should not exceed 50%. A higherrelative humidity is allowed at a lower temperature. For example, the relative humidity at20℃ can reach 90%; for frost due to temperature change, the corresponding measuresshould be taken;
4)The product can withstand the effects of wet air, salt mist, oil mist and mould;
5)The installation category of the circuit breaker connected to the main loop is: Category Ⅲ (power distribution and control level), The installation category of the circuit breaker notconnected to the main loop is: Category Ⅱ (load level);
6)The pollution level is Level 3;
7)The product should be installed in places that are free from explosive media, mediacorrosive to metal, insulation damaging gas, and conductive dust, which should be alsoavoided from snow and rain;
8)In case of stricter user conditions than the above description, negotiate with themanufacturer.




Related recommendations
-
NDG3V-250-800 Isolating Switch
883Applications: The NDG3V-250~800 series switch-disconnectors are applicable to electric systems with a rated voltage up to DC 1500V and a rated current up to 800A. It can be used for in...
View details -
SVM5H-630H/R 1000VAC MCCB
511General SVM5H series of moulded case circuit breaker is supplied with rated insulating voltage 1150V and used for circuit of A.C. 50Hz, rated operating voltage AC 1140V. (or below), rated ...
View details -
NDB1-40 MCB miniature circuit breaker
6591.Application Scope Short-circuit protection Over-load protection Isolation NDB1-40 dedicated to the low voltage power distribution system of industrial, buildings, energy, c...
View details -
NDB1LE-100
191Application●Short-circuit protection●Over-load protection●Earth leakage protection●Isolation protectionNDB1LE-40 series residual current unit is applied to protect direct or indirect earth lea...
View details
HelloPlease log in